Innovation for Modern Problems: The Low Vacuum Anti Siphon Valve

NEW PRODUCT ALERT!

Background: In the past, using anti siphon valves between the day tank and a generator has been discouraged due to the low vacuum capability of generator pumps. A generator fuel oil pump may only be able to pull 5 in. Hg. In addition, there is a filter installed between the day tank and the generator pump that takes a 2-3” Hg pressure drop. This means that only 2” Hg could be available to open an anti-siphon valve, which poses a problem for most designs. Engineers have addressed the need to prevent siphoning from a day tank by installing a solenoid valve that opens when the generator pump turns on. However, this solenoid needs to be wired and is dependent on the controls functioning properly.

Solution: Now, Preferred has a better solution! We now have an anti-siphon valve that will open with only 2” Hg of suction available, and it is designed for application between the day tank and the generator pump. In addition, this Low Vacuum Anti Siphon Valve is UL Listed. For diesel handling components, it is important to ensure the valves one is purchasing are listed by a an agency such as UL as it ensures compliance to a standard and that the product has been independently evaluated. This Low Vacuum Anti Siphon Valve is available in ½” up to 2” NPT.